What size lithium battery for a 5 KVA inverter?

For most 5 KVA, 48 V inverters, one 10 to 16 kWh LiFePO4 battery at 51.2 V is the starting point. Here is how the inverter label, the current and the backup hours decide it.

The short answer: for a 5 KVA inverter on 48 V, start with one 51.2 V LiFePO4 battery of 10, 15 or 16 kWh. It supplies the inverter’s full power at about its recommended current and gives roughly 7 to 12 hours at an average load of 1 kW. Add a second unit if the inverter will run near full power for hours, or if you need longer backup.

Step 1: Read the inverter label

  • kW, not only KVA. 5 KVA is apparent power. The real output in kW is on the same label or datasheet: older designs often list 5 KVA / 4 kW, many newer hybrid inverters 5 KVA / 5 kW. Size the battery on the kW figure.
  • Battery voltage. Most 5 KVA inverters run on 48 V, which in lithium means a 51.2 V battery. If the label says 24 V, you need a 25.6 V battery instead: see our 24 V packs.
  • Battery type setting. Check that the inverter has a lithium setting, or user-defined charge voltages, or a CAN / RS485 port to talk to the battery.

Step 2: Check the battery current

At 51.2 V, each kW of inverter output draws about 20 A from the battery, allowing about 95% inverter efficiency. Near the end of a discharge the battery voltage is lower, so the current is a few percent higher.

Inverter outputBattery current at 51.2 V
2 kWabout 41 A
3 kWabout 62 A
4 kWabout 82 A
5 kWabout 103 A

Our 5 kWh units are rated 50–70 A recommended and 100 A maximum; our 10–20 kWh units 100 A recommended and 200 A maximum. So a single 5 kWh unit would run at its maximum when a 5 KVA inverter delivers full power. For a 5 KVA inverter, choose one 10 kWh unit or larger, or two 5 kWh units in parallel.

Step 3: Decide how many hours you need

Average load10 kWh15 kWh16 kWh20 kWh
500 W14.7 h22.1 h23.2 h29.5 h
1,000 W7.4 h11.1 h11.6 h14.7 h
1,500 W4.9 h7.4 h7.7 h9.8 h
2,000 W3.7 h5.5 h5.8 h7.4 h
3,000 W2.5 h3.7 h3.9 h4.9 h

Using 80% of the rated energy and 90% inverter efficiency. Real runtime also depends on temperature and the inverter’s own consumption.

Our suggestion for a 5 KVA inverter

How the inverter is usedBattery
Lights, fans, TV, Wi-Fi and a fridge through power cuts (about 300–800 W average)One 10 kWh unit
Daily use with some heavy loads, or long outagesOne 15 or 16 kWh unit
Air conditioning or pumping near full power for hoursTwo units in parallel: 2 × 10 kWh or 2 × 16 kWh

Bigger and smaller inverters

  • 3.5 KVA: one 10 kWh unit, or two 5 kWh units in parallel.
  • 7.5 KVA: one 16 or 20 kWh unit, or two 10 kWh units if it runs near full power for hours.
  • 10 KVA: two 10–20 kWh units in parallel, so each stays near its recommended 100 A.

Mistakes to avoid

  • Sizing on KVA. Use the kW output; it is often lower than the KVA figure.
  • Leaving lead-acid charge settings. Set the battery type to lithium, or set the charge voltage yourself. It must not go above 58.4 V on our 51.2 V models.
  • Too much charge current. Set the inverter’s maximum charge current to the battery’s recommended figure: 100 A for our 10–20 kWh units, 50 A for most 5 kWh units.