The short answer: for a 5 KVA inverter on 48 V, start with one 51.2 V LiFePO4 battery of 10, 15 or 16 kWh. It supplies the inverter’s full power at about its recommended current and gives roughly 7 to 12 hours at an average load of 1 kW. Add a second unit if the inverter will run near full power for hours, or if you need longer backup.
Step 1: Read the inverter label
- kW, not only KVA. 5 KVA is apparent power. The real output in kW is on the same label or datasheet: older designs often list 5 KVA / 4 kW, many newer hybrid inverters 5 KVA / 5 kW. Size the battery on the kW figure.
- Battery voltage. Most 5 KVA inverters run on 48 V, which in lithium means a 51.2 V battery. If the label says 24 V, you need a 25.6 V battery instead: see our 24 V packs.
- Battery type setting. Check that the inverter has a lithium setting, or user-defined charge voltages, or a CAN / RS485 port to talk to the battery.
Step 2: Check the battery current
At 51.2 V, each kW of inverter output draws about 20 A from the battery, allowing about 95% inverter efficiency. Near the end of a discharge the battery voltage is lower, so the current is a few percent higher.
| Inverter output | Battery current at 51.2 V |
|---|---|
| 2 kW | about 41 A |
| 3 kW | about 62 A |
| 4 kW | about 82 A |
| 5 kW | about 103 A |
Our 5 kWh units are rated 50–70 A recommended and 100 A maximum; our 10–20 kWh units 100 A recommended and 200 A maximum. So a single 5 kWh unit would run at its maximum when a 5 KVA inverter delivers full power. For a 5 KVA inverter, choose one 10 kWh unit or larger, or two 5 kWh units in parallel.
Step 3: Decide how many hours you need
| Average load | 10 kWh | 15 kWh | 16 kWh | 20 kWh |
|---|---|---|---|---|
| 500 W | 14.7 h | 22.1 h | 23.2 h | 29.5 h |
| 1,000 W | 7.4 h | 11.1 h | 11.6 h | 14.7 h |
| 1,500 W | 4.9 h | 7.4 h | 7.7 h | 9.8 h |
| 2,000 W | 3.7 h | 5.5 h | 5.8 h | 7.4 h |
| 3,000 W | 2.5 h | 3.7 h | 3.9 h | 4.9 h |
Using 80% of the rated energy and 90% inverter efficiency. Real runtime also depends on temperature and the inverter’s own consumption.
Our suggestion for a 5 KVA inverter
| How the inverter is used | Battery |
|---|---|
| Lights, fans, TV, Wi-Fi and a fridge through power cuts (about 300–800 W average) | One 10 kWh unit |
| Daily use with some heavy loads, or long outages | One 15 or 16 kWh unit |
| Air conditioning or pumping near full power for hours | Two units in parallel: 2 × 10 kWh or 2 × 16 kWh |
Bigger and smaller inverters
- 3.5 KVA: one 10 kWh unit, or two 5 kWh units in parallel.
- 7.5 KVA: one 16 or 20 kWh unit, or two 10 kWh units if it runs near full power for hours.
- 10 KVA: two 10–20 kWh units in parallel, so each stays near its recommended 100 A.
Mistakes to avoid
- Sizing on KVA. Use the kW output; it is often lower than the KVA figure.
- Leaving lead-acid charge settings. Set the battery type to lithium, or set the charge voltage yourself. It must not go above 58.4 V on our 51.2 V models.
- Too much charge current. Set the inverter’s maximum charge current to the battery’s recommended figure: 100 A for our 10–20 kWh units, 50 A for most 5 kWh units.