The short answer: a 10.24 kWh battery runs a steady 1 kW load for about 8 hours, a 300 W load for about 27 hours, and a 2 kW load for about 4 hours. Those figures use 80% of the stored energy, before inverter losses. For a home running only essentials (lights, fans, a fridge, TV and Wi-Fi, about 300 to 500 W), that is roughly 16 to 27 hours.
The formula
Hours = rated kWh × 0.8 × inverter efficiency ÷ load in kW. With a 10.24 kWh battery, 80% usable and 90% inverter efficiency, that is 7.4 kWh of AC energy to spend.
Runtime at different loads
| Average load | Before inverter losses | With 90% inverter efficiency |
|---|---|---|
| 100 W | 81.9 h | 73.7 h |
| 300 W | 27.3 h | 24.6 h |
| 500 W | 16.4 h | 14.7 h |
| 1,000 W | 8.2 h | 7.4 h |
| 1,500 W | 5.5 h | 4.9 h |
| 2,000 W | 4.1 h | 3.7 h |
| 3,000 W | 2.7 h | 2.5 h |
| 5,000 W | 1.6 h | 1.5 h |
10.24 kWh battery (51.2 V, 200 Ah), 80% usable. Real runtime also depends on temperature and the inverter’s own consumption.
What typical appliances draw
| Appliance | Typical power |
|---|---|
| LED bulb | 5–10 W each |
| Wi-Fi router | 10–15 W |
| Laptop | 40–65 W |
| LED TV, 43 inch | 60–100 W |
| Fan | 40–75 W |
| Fridge or chest freezer | 100–200 W while the compressor runs; about 40–60 W on average over a day |
| Water pump, 0.5–1 HP | 370–750 W while running |
| Air conditioner, 1.5 HP | 1,100–1,400 W; less for inverter types at part load |
| Microwave | 1,000–1,200 W |
| Kettle | 1,800–2,200 W |
An example evening
Ten LED bulbs (80 W), a TV (80 W), two fans (120 W), a fridge averaging 50 W and a Wi-Fi router (10 W) add up to about 340 W. A 10 kWh battery runs that for about 22 hours after inverter losses: a whole night and most of the next day.
Add a 1.5 HP air conditioner at about 1,200 W and the total becomes about 1.5 kW, which brings the runtime down to about 5 hours.
What shortens or extends runtime
- Heavy loads. Air conditioners, pumps, kettles and irons use most of the energy. Running them while the sun is up saves the battery for the night.
- Cold. LiFePO4 batteries deliver less energy in the cold. Ours discharge from -20 °C but charge only from 0 °C.
- Reserve settings. Many inverters keep a reserve, such as 20%, for backup. That energy is not used in daily cycling.
- Solar. With panels recharging the battery each day, a 10 kWh battery only has to cover the hours without sun.
- A second battery. Two 10 kWh units in parallel double the runtime and halve the current each one supplies.